5/16/2014

Operation and Maintenance of Chillers Part 2

Operation and Maintenance of Chillers
 Part 2


Maintenance of Chillers 2



Key Components of Mechanical Compression Chillers
Evaporator
Chillers produce chilled water in the evaporator where cold refrigerant flows over the evaporator tube bundle. The refrigerant evaporates (changes into vapor) as the heat is transferred from the water to the refrigerant. The chilled water is then pumped, via the chilled-water distribution system to the building’s

air- handling units.
The chilled water passes through coils in the air-handler to remove heat from the air used to condition spaces throughout the building. The warm water (warmed by the heat transferred from the building ventilation air) returns to the evaporator and the cycle starts over.

Compressor
Vaporized refrigerant leaves the evaporator and travels to the compressor where it is mechanically compressed, and changed into a high-pressure, high-temperature vapor. Upon leaving the compressor, the refrigerant enters the condenser side of the chiller.

Condenser
Inside the water-cooled condenser, hot refrigerant flows around the tubes containing the condenser-loop water. The heat transfers to the water, causing the refrigerant to condense into liquid form. The condenser water is pumped from the condenser bundle to the cooling tower where heat is transferred from the water to the atmosphere. The liquid refrigerant then travels to the expansion valve.

Expansion valve
The refrigerant flows into the evaporator through the expansion valve or metering device. This valve controls the rate of cooling. Once through the valve, the refrigerant expands to a lower pressure and a much lower temperature. It flows around the evaporator tubes, absorbing the heat of the chilled water that’s been returned from the air handlers, completing the refrigeration cycle.

Controls
Newer chillers are controlled by sophisticated, on-board microprocessors. Chiller control systems include safety and operating controls. If the equipment malfunctions, the safety control shuts the chiller down to prevent serious damage to the machine. Operating controls allow adjustments to some chiller operating parameters. To better monitor chiller performance, the chiller control system should communicate with the facility’s direct digital control (DDC).


Safety Issues
Chillers are typically located in a mechanical equipment rooms. Each type of refrigerant used in a chiller compressor has specific safety requirements for leak detection and emergency ventilation. Consult your local mechanical code or the International Mechanical Code for details.
The EPA has enacted regulations regarding the use and handling of refrigerants to comply with the Clean Air Act of 1990. All personnel working with refrigerants covered by this act must be appropriately licensed.

Best Practices for Efficient Operation
The following best practices can improve chiller performance and reduce operating costs:
Operate multiple chillers for peak efficiency: 
 Plants with two or more chillers can save energy by matching the building loads to the most efficient combination of one or more chillers. In general, the most efficient chiller should be first one used.
Raise chilled-water temperature: 
 An increase in the temperature of the chilled water supplied to the building’s air handlers will improve its efficiency. Establish a chilled-water reset schedule. A reset schedule can typically adjust the chilled-water temperature as the outside-air temperature changes. On a centrifugal chiller, increasing the temperature of chilled water supply by 2–3°F will reduce chiller energy use 3–5%.
Reduce condenser water temperature: 
 Reducing the temperature of the water returning from the cooling tower to the chiller condenser by 2–3°F will reduce chiller energy use 2–3%. The temperature
setpoint for the water leaving the cooling tower should be as low as the chiller manufacturer will allow for water entering the condenser. The actual leaving tower water temperature may be limited by the ambient wet bulb temperature.
Purge air from refrigerant: 
 Air trapped in the refrigerant loop increases pressure at the compressor discharge. This increases the work required from the compressor. Newer chillers have automatic air purgers that have run-time meters. Daily or weekly tracking of run time will show if a leak has developed that permits air to enter the system.
Optimize free cooling: 
If your system has a chiller bypass and heat exchanger, known as a water-side economizer, it should be used to serve process loads during the winter season. The water-side economizer produces chilled water without running the chiller. Condenser water circulates through the cooling tower to reject heat, and then goes to a heat exchanger (bypassing the chiller) where the water is cooled sufficiently to meet the cooling loads.
Verify Performance of hot-gas bypass and unloader: 
These are most commonly found on reciprocating compressors to control capacity. Make sure they operate properly.
Maintain refrigerant level: 
To maintain a chiller's efficiency, check the refrigerant sight-glass and the superheat and subcooling temperature readings, and compare them to the manufacturer’s requirements. Both low-level and high-level refrigerant conditions can be detected this way. Either condition reduces a chiller’s capacity and efficiency.
Maintain a daily log: 
 Chiller O&M best practices begin with maintaining a daily log of temperatures, fluid levels, pressures, flow rates, and motor amperage. Taken together, these readings serve as a valuable baseline reference for operating the system and troubleshooting problems. Many newer chillers automatically save logs of these measurements in their on-board control system, which may be able to communicate directly with the DDC system. Below is an example of a daily log that can be adapted for use with your chiller.

Sample Operating Log for Chillers
Operating Log for Chillers
 Best Practices for Maintenance
Compared to a major chiller failure, a sound preventive and predictive maintenance program is a minor cost. Implementing a best-practice maintenance plan will save money over the life of the chiller and ensure longer chiller life. For more information on this topic go to Best Practice O&M Program.
Substandard operating practices frequently go unnoticed and become the accepted norm. Training

 personnel in both maintenance and operating practices is the best prevention. Many chiller manufacturers offer training for building operating engineers in operating and maintaining their chillers.
To effectively maintain chillers, you must 1) bring the chiller to peak efficiency, and 2) maintain that peak efficiency. There are some basic steps that facilities professionals can take to make sure their chillers are being maintained properly. Below are some of the key practices.
Reduce Scale or Fouling
Failure of the heat exchanger tubes is costly and disruptive. The evaporator and condenser tube bundles collect mineral and sludge deposits from the water. Scale buildup promotes corrosion that can lead to the failure of the tube wall. Scale buildup also insulates the tubes in the heat exchanger reducing the efficiency of the chiller. There are two main preventive actions:
Checking water treatment: Checking the water treatment of the condenser-water open loop weekly will reduce the frequency of condenser tube cleaning and the possibility of a tube failure.
Checking the water treatment of the chilled-water closed loop monthly will reduce the frequency of evaporator tube cleaning and the possibility of a tube failure.
Inspecting and cleaning tubes: The tubes in the evaporator and condenser bundles should be inspected once a year, typically when the chiller is taken offline for winterizing. Alternately, for systems that operate all year to meet process loads, tube scaling and fouling can be monitored by logging pressure drop across the condenser and evaporator bundles. An increase in pressure from the inlet to the        outlet of 3–4 PSI indicates a probable increase in scale or fouling requiring tube cleaning.

Inspect for Refrigerant Leaks
If possible, monitor the air-purge run timer. Excessive or increased air-purge time may indicate a refrigerant leak. If an air-purge device is not installed, bubbles in the refrigerant sight-glass may also indicate refrigerant leak. Gas analyzers can also be used to identify refrigerant leaks.
The table below provides a checklist for maintenance tasks.

   abo bahaa eddine






5 comments:

  1. Thanks for sharing excellent information. Your web-site is very cool. I'm impressed by the details that you have on this web site. It reveals how nicely you perceive this subject. Air Dryer Manufacturer || Air Dryer || Air Dryer Manufacturers

    ReplyDelete
  2. Have you ever thought about creating an ebook or guest authoring on other websites?
    I have a blog centered on the same subjects you discuss and would love
    to have you share some stories/information. I know my
    readers would value your work. If you're even remotely interested, feel free to shoot me
    an e-mail.

    Here is my website :: cheap website maintenance company

    ReplyDelete
  3. Very nice post. I simply stumbled upon your blog and wished to mention that I've truly loved browsing your weblog posts.
    In any case I will be subscribing on your feed and I'm hoping you write again soon!

    Also visit my blog post: AC Repair Thousand Oaks - Ventura No Air

    ReplyDelete
  4. I’m not that much of a online reader to be honest but your blogs really nice, keep it up!
    I'll go ahead and bookmark your website to come back down the road.

    Many thanks

    Also visit my web-site - AC Repair Thousand Oaks - Cooling Thousand oaks

    ReplyDelete
  5. The best thing yߋu can do ffor your wallet and your homes maintenance when it comes to spotting a plumbing fault,
    is to call out a рrofessionql plumbing servіce immediately.

    Although hard cokre gamers are usually disappointed byƴ the lack of more serious games, they are not entirely absent from the Wii platform.
    When installing pipеs, plumbeгs are cazlled beccause without the proper installatiօn oof pipes,
    we cannot have proper water supply and sanitɑtion in ourг offices and homes.
    Ƭhe Price Pfister two handle "Verve" shoԝeг valve is
    very reliable faucet. ProviԀed these are disclosed as pardt of the leaѕe aɡreement, these aree legal charges tenants
    are obligated to pay. Properties let as holiday cottages can need
    sеrvices from an plumbing expert. Click here to find oսt whhy your աater heater may not be working aas
    efficiently аs it should. It could also result in needing
    to get the furniture fixeԁ. Howevеr, we tеnd to forget
    about heating systems in thee height of sunmer when everyone just wɑnts tօ be outside in the fresh air.
    If you hope to buy a new manufactured home, it is beest tto carefully
    checҡ out the model of the home with the retaіleг.

    My wеb sitе - Slab Leak Grant Seafood Festival

    ReplyDelete